312785C
EN
Instructions-Parts
Gateway Network
Communication Kits
Installation and program setup instructions for use with ProMix
®
2KS Electronic
Proportioners. For professional use only.
Not approved for use in European explosive atmosphere locations.
See page 3 for kit information.
Important Safety Instructions
Read all warnings and instructions in this manual
and in your proportioning system manual. Save
these instructions.
TI12933b
Vista de pagina 0
1 2 3 4 5 6 ... 81 82

Indice de contenidos

Pagina 1 - Communication Kits

312785CENInstructions-PartsGateway Network Communication KitsInstallation and program setup instructions for use with ProMix® 2KS Electronic Proportio

Pagina 2 - Contents

Install the Gateway Module Hardware 10 312785CFIG. 6: Programming PortsTI13969aGreen/Amber LEDRS232/PGUSB/PGETHERNETORORYellow LEDFIG. 7: RS232/PG Com

Pagina 3 - Related Manuals

Install the Gateway Module Hardware312785C 11Mount the Control on DIN RailThe Gateway control mounts on a DIN rail. Tilt the con-trol and push down on

Pagina 4 - Warnings

Install the GracoConfig Software 12 312785CInstall the GracoConfig SoftwareGracoConfig software provides access to the Graco Gateway module hardware.

Pagina 5 - Module Hardware

Install the GracoConfig Software312785C 13Load the Software1. Connect the USB cable (23, supplied) between the USB port on the Gateway module and a US

Pagina 6 - 6 312785C

Install the GracoConfig Software 14 312785CDownload the Preconfigured Database to the Gateway ModuleGraco supplies a preconfigured database as a setup

Pagina 7 - Cabling Connections

Graco Gateway Network Communications Configuration312785C 15Graco Gateway Network Communications ConfigurationStartupTo run GracoConfig, select the ic

Pagina 8 - 8 312785C

Graco Gateway Network Communications Configuration 16 312785CSetup the Database1. Double-click on the Communications button to open the preconfigured

Pagina 9 - 312785C 9

Graco Gateway Network Communications Configuration312785C 173. See FIG. 20. Right click on device PLC1 to rename it to something meaningful for your s

Pagina 10 - 10 312785C

Graco Gateway Network Communications Configuration 18 312785CMap Data1. See FIG. 22. Select the block for data mapping. Click the Edit button next to

Pagina 11 - Install CompactFlash

Graco Gateway Network Communications Configuration312785C 193. See FIG. 23. Click the Edit button next to the Block Size field on the right side of th

Pagina 12 - System Requirements

2 312785CContentsGraco Gateway Kits . . . . . . . . . . . . . . . . . . . . . . . . . 3Related Manuals . . . . . . . . . . . . . . . . . . . . . .

Pagina 13 - Software Updates

Graco Gateway Network Communications Configuration 20 312785C4. See FIG. 24. Click OK. The range of addresses will appear under the appropriate Block

Pagina 14 - Download the Preconfigured

Modbus and I/O Data312785C 21Modbus and I/O DataSee Table 4 through Table 5 for Modbus register addresses and input/output data.Reference the Discrete

Pagina 15 - Configuration

Modbus and I/O Data 22 312785CFIG. 25. Start Mix Mode Process Flow ChartStart Mix Mode ProcessIs Mix Ready bit = 1?Must be Alarm Condi-tion or Active

Pagina 16 - Setup the Database

Modbus and I/O Data312785C 23FIG. 26. Mixing Mode Process Flow ChartMixing Mode ProcessIs Mix Active bit = 1?Check AlarmCondition: is Alarm_General bi

Pagina 17 - 312785C 17

Modbus and I/O Data 24 312785CFIG. 27. Purge Mode Process Flow ChartStartIs Mix Ready bit = 1?Must be AlarmCondition or Active Recipe 61. See Alarm Pr

Pagina 18 - Map Data

Modbus and I/O Data312785C 25FIG. 28. Color Change Mode Process Flow ChartProcess Alarm. See Alarm Processing, page 26.Color Change Process (basic)Is

Pagina 19 - 312785C 19

Modbus and I/O Data 26 312785CAlarm ProcessingSee FIG. 29, Table 1, Table 2, and Table 3.FIG. 29. Alarm Processing Flow ChartAlarm ProcessingIs Mix Re

Pagina 20 - 20 312785C

Modbus and I/O Data312785C 27NOTE: Shaded cells relate to the flow charts on pages 23-26.Table 1: ProMix 2KS Digital Inputs (Modbus Register 40040)Bit

Pagina 21 - Modbus and I/O Data

Modbus and I/O Data 28 312785CNOTE: Shaded cells relate to the flow charts on pages 23-26.Table 2: ProMix 2KS Digital Outputs (Modbus Register 40041)B

Pagina 22

Modbus and I/O Data312785C 29ProMix 2KS Active Alarms (Modbus Register 40010)Table 3: ProMix 2KS Active Alarms (Modbus Register 40010)Bit Digital Inpu

Pagina 23

Graco Gateway Kits312785C 3Graco Gateway Kits15V331 Gateway Ethernet KitAllows communication between ProMix 2KS and a PLC over an ethernet. Enables pr

Pagina 24

Modbus and I/O Data 30 312785CProMix 2KS Modbus/TCP Variable Map* This column represents the rule that must be implemented by automation. Writing to R

Pagina 25

Modbus and I/O Data312785C 31ProMix 2KS Recipe BitsTable 5: ProMix 2KS Recipe BitsRecipe Bits NumberRecipe Bits Number543210 543210000000 0 100001 330

Pagina 26 - Alarm Processing

Troubleshooting 32 312785CTroubleshooting NOTE: This section covers the most common problems encountered while setting up, programming or using the pr

Pagina 27 - 312785C 27

Troubleshooting312785C 33Unit shows “Version Mismatch”. The database currently in the device does not match Graco Gateway’s firmware version. (Message

Pagina 28 - 28 312785C

Troubleshooting 34 312785CSymbol or image leaves a trace when animated.The background of the image is not refreshed.Change the primitive Fill Format t

Pagina 29 - 312785C 29

Troubleshooting312785C 35Graco Gateway Messages Troubleshooting PROBLEM CAUSE SOLUTIONDevice incompatible with file. The device you are trying to down

Pagina 30 - 30 312785C

Troubleshooting 36 312785CSerial Communication TroubleshootingThis section is used to troubleshoot the communication between two devices linked via se

Pagina 31 - ProMix 2KS Recipe Bits

Troubleshooting312785C 37Ethernet Communication Troubleshooting This section is used to troubleshoot the communication between two devices linked via

Pagina 32 - Troubleshooting

Troubleshooting 38 312785CLED FunctionsStatus (STS) LEDThe green Status LED provides information on the sta-tus of the Graco Gateway, including variou

Pagina 33 - 312785C 33

System Electrical Schematic312785C 39System Electrical SchematicNon-Hazardous AreaBARRIERBOARDOPERATOR INTERFACE12L1N85-250 VACGND N L1 85-250 VAC12

Pagina 34 - 34 312785C

Warnings 4 312785CWarningsThe following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama-tion point

Pagina 35 - 312785C 35

Parts 40 312785CParts15V331 Gateway Ethernet Kit (shown)15V963 Gateway DeviceNet Kit15V964 Gateway Profibus Kit▲ Replacement Danger and Warning labels

Pagina 36 - 36 312785C

Parts312785C 41TI12930aTI12932aTI12929a345681011121314151714181817147, 9, 121, 2To 4To 10Wiring DiagramsTI12931a12345678shsh123ASHBProMix 2KS EasyKey

Pagina 37 - 312785C 37

Appendix A: DeviceNet™ Slave Communication 42 312785CAppendix A: DeviceNet™ Slave CommunicationOverviewThis appendix describes the Gateway’s support f

Pagina 38 - LED Functions

Appendix A: DeviceNet™ Slave Communication312785C 43FIG. 30: DeviceNet Port Pin Outs and PLC ConnectionXCDNNET STSCAN_LDRAINCAN_HV+V-V-LEDCAN_LDRAINCA

Pagina 39 - System Electrical Schematic

Appendix A: DeviceNet™ Slave Communication 44 312785CAbout DeviceNetDeviceNet is a connection-based network. In this con-text the term connection refe

Pagina 40 - 15V964 Gateway Profibus Kit

Appendix A: DeviceNet™ Slave Communication312785C 45HardwareTo use DeviceNet on the Gateway, an option card must first be installed. The option card p

Pagina 41 - 312785C 41

Appendix A: DeviceNet™ Slave Communication 46 312785CThe DeviceNet Option card appears at the end of the tree. Select the DeviceNet Interface from und

Pagina 42 - Slave Communication

Appendix A: DeviceNet™ Slave Communication312785C 47IMPORTANT NOTE: The I/O Polled Size is determined by the settings in both the DeviceNet Master and

Pagina 43 - PLC Connection

Appendix A: DeviceNet™ Slave Communication 48 312785CCreate Gateway BlocksSelect the DeviceNet device from the tree at the left, and add two Gateway B

Pagina 44 - About DeviceNet

Appendix A: DeviceNet™ Slave Communication312785C 49NOTE: For 16-bit support, select Word as Word. For 32-bit support, select Word as Long. The latter

Pagina 45 - Hardware

Graco Gateway Overview312785C 5Graco Gateway OverviewThe Graco Gateway enables the ProMix 2KS to network with a programmable logic controller (PLC). K

Pagina 46 - 46 312785C

Appendix A: DeviceNet™ Slave Communication 50 312785CSelect the second Gateway Block and set it up for I/O Polled Response Data 00000, with a length o

Pagina 47 - 312785C 47

Appendix A: DeviceNet™ Slave Communication312785C 51Automatic Update of the EDS FileDeviceNet nodes use an EDS (Electronic Data Sheet) to describe the

Pagina 48 - Create Gateway Blocks

Appendix A: DeviceNet™ Slave Communication 52 312785CConfigure the RSNetWorx for DeviceNet SoftwareRSNetWorx for DeviceNet is used to set up and manag

Pagina 49 - 312785C 49

Appendix A: DeviceNet™ Slave Communication312785C 53Review the EDS registration, and finish the process.Select the DeviceNet Master by navigating in t

Pagina 50 - 50 312785C

Appendix A: DeviceNet™ Slave Communication 54 312785CMake sure that the Strobed or Change of State boxes are not selected. In the Polled section, veri

Pagina 51 - 312785C 51

Appendix A: DeviceNet™ Slave Communication312785C 55Configure the Allen Bradley ControlLogix PLCAllen Bradley ControlLogix PLCs are programmed with RS

Pagina 52 - 52 312785C

Appendix A: DeviceNet™ Slave Communication 56 312785CConfigure the DeviceNet Scanner to be address 0. Make sure to set up the 32-bit Input and Output

Pagina 53 - 312785C 53

Appendix B: Profibus™ DP Slave Communication312785C 57Appendix B: Profibus™ DP Slave CommunicationOverviewThis appendix describes the Gateway’s suppor

Pagina 54 - 54 312785C

Appendix B: Profibus™ DP Slave Communication 58 312785CAbout Profibus DPProfibus DP communication takes the form of block exchange. Profibus blocks ar

Pagina 55 - 312785C 55

Appendix B: Profibus™ DP Slave Communication312785C 59Setup the PLCThe Siemens Simatic Manager software is used to set up the S7300 PLC. The following

Pagina 56 - Wire the DeviceNet Network

Install the Gateway Module Hardware 6 312785CFIG. 1: Graco Gateway Typical Installation TI13939aComputer (PC)Programmable Logic Controller (PLC)Graco

Pagina 57 - DP Slave Communication

Appendix B: Profibus™ DP Slave Communication 60 312785CClick Browse to select the folder were the GSD file downloaded previously is, select the file a

Pagina 58 - About Profibus DP

Appendix B: Profibus™ DP Slave Communication312785C 61Setup the Profibus NetworkThe following steps show how to set up the Profibus DP network. Skip t

Pagina 59 - Setup the PLC

Appendix B: Profibus™ DP Slave Communication 62 312785CIn the General tab, click the properties button to open the Profibus properties. FIG. 53.In the

Pagina 60 - 60 312785C

Appendix B: Profibus™ DP Slave Communication312785C 63Select the Network Settings tab and choose the Trans-mission Rate that fits the application. In

Pagina 61 - Setup the Profibus Network

Appendix B: Profibus™ DP Slave Communication 64 312785CAdd the Graco Gateway to the Profibus NetworkTo add the Graco Gateway to the Profibus network,

Pagina 62 - 62 312785C

Appendix B: Profibus™ DP Slave Communication312785C 65The Gateway is now on the Profibus DP network and selected. HWConfig shows the slots available u

Pagina 63 - 312785C 63

Appendix B: Profibus™ DP Slave Communication 66 312785CGraco Gateway SetupOnce the PLC is setup, the Gateway can be pro-grammed to fit its configurati

Pagina 64 - 64 312785C

Appendix B: Profibus™ DP Slave Communication312785C 67The option card appeared in the communication tree. Select the Profibus Interface and click the

Pagina 65 - 312785C 65

Appendix B: Profibus™ DP Slave Communication 68 312785CSetup TagsOnce the communication is set up, tags can be created to access the PLC blocks. This

Pagina 66 - Graco Gateway Setup

Appendix B: Profibus™ DP Slave Communication312785C 69In the popup window, select the block type required. Two choices are available:• Input block: Th

Pagina 67 - 312785C 67

Install the Gateway Module Hardware312785C 7Connect the Module to the EasyKeyFIG. 1 is only a guide showing installation of the Graco Gateway in a Pro

Pagina 68 - Setup Tags

Appendix B: Profibus™ DP Slave Communication 70 312785CHow Addressing WorksPLC addressing is in byte and uses the scheme shown in FIG. 66.The Gateway

Pagina 69 - 312785C 69

Appendix B: Profibus™ DP Slave Communication312785C 71Useful FormulasThe following formula can be used to find the byte num-ber from a word address:By

Pagina 70 - How Addressing Works

Appendix C: Graco Gateway to ControlLogix via Ethernet IP 72 312785CAppendix C: Graco Gateway to ControlLogix via Ethernet IPOverviewThis appendix des

Pagina 71 - Useful Formulas

Appendix C: Graco Gateway to ControlLogix via Ethernet IP312785C 73ControlLogix Configuration 1. Run the RSLogix 5000 program and create a new configu

Pagina 72 - Ethernet IP

Appendix C: Graco Gateway to ControlLogix via Ethernet IP 74 312785CFIG. 70. Port Configuration WindowIP AddressSubnet MaskSet ButtonFIG. 71. Ethernet

Pagina 73 - ControlLogix Configuration

Appendix C: Graco Gateway to ControlLogix via Ethernet IP312785C 75e. In the Name field, enter a descriptive name to identify the module. See FIG. 72.

Pagina 74 - 74 312785C

Appendix C: Graco Gateway to ControlLogix via Ethernet IP 76 312785CSee FIG. 73. You should now see a new ETHER-NET-MODULE Gateway_HMI branch of the 1

Pagina 75 - 312785C 75

Appendix C: Graco Gateway to ControlLogix via Ethernet IP312785C 77Graco Gateway Configuration 1. Ethernet Settings. Set the IP Address to 192.168.2.1

Pagina 76 - 76 312785C

Appendix C: Graco Gateway to ControlLogix via Ethernet IP 78 312785CThe following settings mirror the I/O settings of the ControlLogix configuration d

Pagina 77 - Graco Gateway Configuration

Dimensions312785C 79DimensionsTI12825b16.57 in. (420.9 mm)15.07 in. (382.8 mm)4.52 in. (114.8 mm)5.31in. (134.9 mm)8.71in. (221.2 mm)TI12930a

Pagina 78 - 78 312785C

Install the Gateway Module Hardware 8 312785CFIG. 3: EasyKey and Module Cable Connection PointsTI12930aTI12638a2-wire twisted pair cable, withshield w

Pagina 79 - Dimensions

Dimensions 80 312785C

Pagina 80 - 80 312785C

Technical Data312785C 81Technical DataElectrical power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Vdc, +/- 10%. 200 mA minimum withou

Pagina 81 - Technical Data

All written and visual data contained in this document reflects the latest product information available at the time of publication. Graco reserves th

Pagina 82 - Graco Information

Install the Gateway Module Hardware312785C 9FIG. 4: Graco Gateway Port Pin OutsTI13974aGreen/Amber LEDRS232/PGUSB/PGETHERNET (NIC)Ye l lo w LEDCOMMSCO