Alarms
30 313528E
Fluid Control Module (continued)
DD1X
DD2X
A - Pump Diving
B - Pump Diving
Pump leak. Worn valve or packings.
See Check-Mate Displace-
ment Pump manual.
Cleared from Ram Alarm
screen. See Appendix A -
User Interface Display,
page 31.
Ram air pressure set too low. Increase air pressure to
ram until diving stops.
Material flow rate exceeds
ability of ram to feed pump.
Decrease pump air pres-
sure to slow cycle rate.
Decrease pressure until
diving stops.
001X
002X
A - Platen Seals Mainte-
nance Reset
or
A- Pump Maintenance
Reset
B - Platen Seals Mainte-
nance Reset
or
B- Pump Maintenance
Reset
Reminder when maintenance
counter was last reset.
Reset on Maintenance
Screen 2.
Cleared when reset from
Maintenance Screen 2.
MGDX Filter Pressure Drop Low Pressure drop from filter inlet
to outlet is below minimum
drop setpoint for 10 consecu-
tive cycles. Filter element has
collapsed or is not present.
Replace filter element. Cleared when reset from
Status Screen 2.
Filter Pressure Drop High Pressure drop from filter inlet
to outlet is above maximum
drop setpoint for 10 consecu-
tive cycles. Filter is clogged.
Remove and clean filter. Cleared when reset from
Status Screen 2.
Alarm
Code Alarm Problem Cause Solution Clear Alarm